5.2 Menu Options and Settings
5.2.1 Main Menu
The MAIN MENU consists of 4 sub menus which are shown below and detailed on the
following pages.
MAIN MENU
1. SELECT 3. DISPLAY
2. UNITS 4. SETUP
All sub-menus are accessed using and exited using
The and keys move the cursor within a menu and allow
parameters to be changed.
TIP Holding down one of these keys scrolls through the data quicker.
5.2.2 Select Menu
FUEL
O2 Ref
SMOKE
RESET
: NATURAL GAS
: OFF
: OFF
: NO
This menu allows selections to be made for the parameters detailed below.
FUEL : Select the fuel being used by the boiler from either a standard fuel stored in the
analyser or by entering the user fuel. Once the correct fuel has been selected
press to view the fuel constants.
NATURAL GAS
K1g
K_2
K_4
: 0.350
: 11.89
: 32
K1n
K_3
O2r
: 0.390
: 9.83
: 3.0